①
Distance
⑤
Lower calibration point
②
Space
⑥
Far range
③
Upper calibration point
⑦
Level
④
Sensor reference point
Setting
Description
Reference point
Level
LEVEL
Height of material
Lower calibration point (process
empty level)
Space
SPACE
Distance to material surface
Upper calibration point (process
full level)
Distance
DIST
Sensor reference point
Custom
CUSTM
Linearization table (level/volume
or level/flow breakpoints)
Lower calibration point
Material type
Used to optimize performance based on material type.
Setting
Liquid
LQD
Solid
SOLID
Default
Liquid
LQD
Units
Sets measurement units used.
Default
Setting
Meters
m
3 decimal places
Centimeters
cm
1 decimal place
Millimeters
mm
0 decimal places
Feet
Ft
3 decimal places
Inches
in
2 decimal places
Default
Meters
m
3 decimal places
Commissioning
7.2 Local commissioning
SITRANS Probe LU240 with mA/HART
Compact Operating Instructions, 10/2018, A5E42673704-AB
37