Connecting
4
4.1
Basic safety notes
WARNING
Incorrect conduit system
Risk of explosion in hazardous areas as result of open cable inlet or incorrect conduit
system.
•
In the case of a conduit system, mount a spark barrier at a defined distance from the
device input. Observe national regulations and the requirements stated in the relevant
approvals.
See also
Technical specifications (Page 38)
WARNING
Hazardous contact voltage
Risk of electric shock in case of incorrect connection.
•
For the electrical connection specifications, refer to the information in Technical
specifications (Page 38).
•
At the mounting location of the device observe the applicable directives and laws for
installation of electrical power installations with rated voltages below 1000 V.
WARNING
Unprotected cable ends
Risk of explosion through unprotected cable ends in hazardous areas.
•
Protect unused cable ends in accordance with IEC/EN 60079-14.