Commissioning
6.3 Empty Pipe Set
FUH1010 IP65 NEMA 4X Precision Volume
Operating Instructions, 01/2013, A5E32122003-AA
75
See also
Refer to I/O Connections and Wiring (Page 163) for input/output wiring and Span Data
(Page 94) for data spanning procedures.
6.3
Empty Pipe Set
The flow meter performs the MTYmatic routine automatically during its Initial Make-up to
establish a standard setting for the Empty Pipe alarm. This process is normally sufficient for
setting this parameter. The [Empty Pipe Set] option list allows you to re-invoke MTYmatic,
use an Actual MTY routine (if application conditions allow you to empty and refill the pipe) or
use the Set Empty routine to set the empty pipe threshold by direct numeric entry.
Actual MTY Command
If application conditions allow you to empty and refill the pipe, then you may choose to
perform the Actual Empty procedure; however, it is not required to do so.
Note
IMPORTANT
NEVER perform the Actual MTY procedure if the pipe can not be emptied.
To use the Actual MTY command:
1.
From [Channel Setup] scroll down to [Install Sensor].
2.
Press the <Right Arrow> to access the [Empty Pipe Set] option list.
3.
Press the <Down Arrow> to [Actual MTY] then press <ENTER>.
–
Empty Pipe Press [ENT] appears on the menu prompt line.
6LHPHQV
'XDO3DWK>@$%&
(PSW\3LSH
3UHVV>(17@
,QVWDOO6HQVRU
,QVWDOO3DWK
6HQVRU0RGHO
+37
6HQVRU6L]H
'+
6HQVRU0RXQW0RGH
5HIOHFW
6SDFLQJ2IIVHW
1RUPDO
1XPEHU,QGH[
6SDFLQJ0HWKRG
6SDFHU%DU%1
/WQ9DOXHLQ
(PSW\3LSH6HW
07<PDWLF
=HUR)ORZ$GMXVW
!$FWXDO07<
,QVWDOO&RPSOHWH
6HW(PSW\
Summary of Contents for SITRANS FUH1010
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ...21614 C 1011NFPS 7 ...
Page 232: ...1011NFPS 7 C 21614 ...
Page 233: ...1011NFPS 7 C 21614 ...
Page 234: ...21614 C 1011NFPS 7 ...
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ...21614 C ...
Page 241: ......
Page 242: ......
Page 243: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 244: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 245: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 246: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 251: ......
Page 263: ...Index FUH1010 IP65 NEMA 4X Precision Volume 202 Operating Instructions 01 2013 A5E32122003 AA ...