
5.2.2.5
Connecting the Profibus (CH1)
WARNING
Passive channels only
Channel 1 power supply must be separated from that for channels 2 to 4.
Signal return (or common) can be joined.
1. Remove cap and ferrule from cable gland and slide onto cable.
2. Push cable through open gland and cable path.
3. Restore ferrule and tighten cap to lightly hold cable in place.
4. Signal cable screen is folded back over outer sheath and grounded beneath cable clamp.
Connecting
5.2 Connecting FC330
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
71