Installing/Mounting
2.2 F US Clamp-on Communications Module Installation
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
15
Baud Rate Selection: SW1-A (7-8) - To Network
9600 A7 OFF A8 OFF
19200 A7 ON A8 OFF
38400 A7 OFF A8 ON
76800 A7 ON A8 ON
Profile Selection: SW2-B (1-6)
See selection table 2-1.
Protocol Selection: SW2-B (7-8)
Hart is active at all times. (SW-2 B7 and B8 are not required for HART communication.)
Modbus RTU/Modbus TCP/IP B7 OFF B8 OFF
BACnet IP/BACnet MSTP
B7 ON B8 OFF
Ethernet /IP
B7 OFF B8 ON
N2 Metasys
B7 ON B8 ON
Note
When using the WEB utility there are parameters under View/Data Arrays/ that identify the
position of the DIP switches:
•
DA-DIP: All 16 positions of switches A & B are identified in decimal form
•
DA-DIP_A: All 8 positions of switch are identified in decimal form
•
DA-DIP_B: Positions 1-4 of switch B are identified in decimal form
•
DA-DIP_S: Positions 5-8 of switch B are identified in decimal form
Determine Flowmeter Firmware Version
To determine the firmware version of your flowmeter refer to the table below. The firmware
version is listed in the Meter Facilities menu of the flowmeter and can be located using the
following procedure:
1.
At the meter, press the <MENU> key.
2.
Press the <Down Arrow> and scroll to [Meter Facilities].
3.
Press the <Right Arrow>.
4.
Press the <Down Arrow> and scroll to [System Info].
5.
Press the <Right Arrow> to read your flowmeter version.