Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
159
A.1.40
Profile 39
Profile 39 (FUH1010-5BN02-5.04.05-1CO2CO)
Data Description Modbus
Ethernet/IP
HART
N2
Reg
Bytes Type
Tag Name OS
Format CMD VAR
Type
Ad Sz
C1 Site ID
30501 8
String String_In
0
UINT16
n/a
BD(Byte)
1
8
Date: Year
30101 2
Integer Analog_In
0
Float
n/a
ADI(Int)
1
1
Date: Month
30102 2
Integer Analog_In
1
Float
n/a
ADI(Int)
2
1
Date: Day
30103 2
Integer Analog_In
2
Float
n/a
ADI(Int)
3
1
Time: Hour
30104 2
Integer Analog_In
3
Float
n/a
ADI(Int)
4
1
Time: Minute
30105 2
Integer Analog_In
4
Float
n/a
ADI(Int)
5
1
Time: Second
30106 2
Integer Analog_In
5
Float
n/a
ADI(Int)
6
1
C1 Raw Flow
30133 4
Real
Analog_In
6
Float
n/a
ADF(Float)
1
1
C1 Raw Flow
Units
30537 8
String String_In
4
UINT16
n/a
BD(Byte)
9
8
C1 Sonic Vel
30157 4
Real
Analog_In
7
Float
n/a
ADF(Float)
2
1
C1 Sonic Vel
Units
30577 8
String String_In
8
UINT16
n/a
BD(Byte)
17 8
C1 Signal
Strength
30167 2
Integer Analog_In
8
Float
n/a
ADF(Float)
3
1
C1 Sig Strength
Units
30593 8
String String_In
12
UINT16
n/a
BD(Byte)
25 8
C1 Aeration
30172 2
Integer Analog_In
9
Float
n/a
ADF(Float)
4
1
C1 Aeration Units 30609 8
String String_In
16
UINT16
n/a
BD(Byte)
33 8
C1 Liquid Name 30745 8
String String_In
20
UINT16
n/a
BD(Byte)
41 8
C1 Liquident
30231 4
Real
Analog_In
10
Float
n/a
ADF(Float)
5
1
C1 Liquident
Units
30677 8
String String_In
24
UINT16
n/a
BD(Byte)
49 8
C1 Specific
Gravity
30239 4
Real
Analog_In
11
Float
129 15-0Fh P ADF(Float)
6
1
C1 S.G. Units
30689 8
String String_In
28
UINT16 131 15-0Fh
BD(Byte)
57 8
C1 API
30249 4
Real
Analog_In
12
Float
129 18-12h S ADF(Float)
7
1
C1 API Units
30705 8
String String_In
32
UINT16 131 18-12h
BD(Byte)
65 8
C1 Kg/m3
30255 4
Real
Analog_In
13
Float
129 21-15h
ADF(Float)
8
1
C1 Kg/m3 Units
30713 8
String String_In
36
UINT16 131 21-15h
BD(Byte)
73 8
C1 Base S.G.
30261 4
Real
Analog_In
14
Float
129 24-18h
ADF(Float)
9
1
C1 Base S.G.
Units
30721 8
String String_In
40
UINT16 131 24-18h
BD(Byte)
81 8
C1 Base API
30267 4
Real
Analog_In
15
Float
129 27-1Bh
ADF(Float)
10 1
C1 Base API
Units
30729 8
String String_In
44
UINT16 131 27-1Bh
BD(Byte)
89 8
C1 Base Kg/m3
30273 4
Real
Analog_In
16
Float
129 30-1Eh
ADF(Float)
11 1
C1 Base Kg/m3
Units
30737 8
String String_In
48
UINT16 131 30-1Eh
BD(Byte)
97 8
C1 Status
/Alarms: Spacing
10021 1 Bit
Coil
Binary_In
0
UINT16
n/a
DI(Dig In)
1
1
C1 Status
/Alarms: Empty
10022 1 Bit
Coil
Binary_In
0
UINT16
n/a
DI(Dig In)
3
1