Digital output 1 (Menu item 4.2)
You have the following setting options in this menu:
• Function, menu item 4.2.1
You can configure digital output 1 as a pulse, frequency, alarm or status output
When "Split value active" is selected, the output is active when the current level of the flow
value is within the lower sub domain 0 to
"Split value"; the output current is then scaled to the 0 to "Split value" range. If the flow value
exceeds this sub-domain, the output current is scaled to the 0 to URV range.
• Signal type, menu item 4.2.2
You can configure different signal types for the output signal of digital output 1:
– Active:
The device-internal voltage is used (+24 V).
– Passive:
External supply required.
U
24 V
4 7 8 3 5
U
4 7 8 3 5
I
T
2
T
1
T
2
I
5 (+)
5 (+)
6 (-)
6 (-)
170
˖
①
Active
②
Passive
③
Counter
④
External supply max. DC 30 V
Figure 8-6
Active and passive signals
Functions
8.5 Function Group Device Outputs
TRANSMAG 2 with MAG 911/E
68
Operating Instructions, 03/2021, A5E00102775-AC