Note
Use cables with a cross section of at least 1.5 mm
2
and double or reinforced insulation for the
power supply.
Wiring guidelines
1. Release the catch on the lid of the terminal box using a 3 mm Allen key.
2. Unscrew the lid of the terminal box.
3. Push the supply cable through the cable glands up to the terminal strip. Lay the cable in a loop
before the cable glands so that moisture does not get inside the terminal box.
4. Connect the cables according to the figure below.
①
Ground connection for signal cable shield
②
Digital output 2 (relay) or digital input
③
Digital output 1 (active/passive)
④
Analog output (active) 4 to 20 mA or PROFIBUS
⑤
Power supply: L/N for 100 to 230 V AC
⑥
Terminal for PE conductor
Figure 5-4
Connection diagram for power supply and signal cables
5.4
Step 2: Connecting signal cables
CAUTION
Lay the signal cables separately from cables with voltages > 60 V.
Avoid laying signal cables close to large electrical installations or use - if possible - only shielded
cables.
Note
In a wet environment, the signal cable for digital output 2 (terminals 3 and 4) must be isolated
when the feed-in voltage is more than 16 V AC/35 V DC (16 V RMS/ 22.6 V peak).
Only use signal cables with twisted wire pairs.
Connecting
5.4 Step 2: Connecting signal cables
TRANSMAG 2 with MAG 911/E
36
Operating Instructions, 03/2021, A5E00102775-AC
Summary of Contents for SITRANS F TRANSMAG 2
Page 6: ...Table of contents TRANSMAG 2 with MAG 911 E 6 Operating Instructions 03 2021 A5E00102775 AC ...
Page 92: ...Dimension drawings TRANSMAG 2 with MAG 911 E 92 Operating Instructions 03 2021 A5E00102775 AC ...
Page 104: ...Parameters TRANSMAG 2 with MAG 911 E 104 Operating Instructions 03 2021 A5E00102775 AC ...
Page 126: ...Index TRANSMAG 2 with MAG 911 E 126 Operating Instructions 03 2021 A5E00102775 AC ...