Modbus communication
A.9 Modbus holding registers tables
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
212
Operating Instructions, 08/2017, A5E37367739-AC
Channel 2 pulse output settings
Table A- 51 Channel 2 pulse output settings
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units regis-
ter)
Value range /
Setting options
Access
level
8960
Unsigned / 2 Process value
Select process value
for the pulse output.
0
•
0: Mass flow
•
1: Volume flow
•
27: Standard volume
flow rate (only hydro-
carbon and gas ap-
plications)
Read /
write
8962
Unsigned / 2 Flow direction
Flow direction filter.
0
•
0: Positive direction
•
1: Negative direction
•
2: Positive and nega-
tive directions
Read /
write
8965
Float / 4
Amount of vol-
ume
Amount value to gen-
erate an output pulse.
Applicable if Process
value (8960) is set to 1.
0.001
[m
3
]
(8993)
-
Read /
write
8963
Float / 4
Amount of
mass
Amount value to gen-
erate an output pulse.
Applicable if Process
value (8960) is set to 0.
1.0
[kg]
(8992)
-
Read /
write
8967
Float / 4
Amount of
standard vol-
ume
Amount value to gen-
erate an output pulse.
Applicable if Process
value (8960) is set to
27.
1.0
[NI]
(8994)
-
Read /
write
10055
Unsigned / 2 Pulses per
amount
Number of pulses
which will be output
when configured
amount is reached.
1
-
Read /
write
8974
Float / 4
Pulse width
Pulse duration.
0.1
[s]
0.00004 - 4.0
Read /
write
8977
Unsigned / 2 Polarity
Logical polarity of
pulse output.
0
•
0: Active high level
•
1: Active low level
Read /
write