Symptom
Output sig‐
nals
Error code Cause
Remedy
Measuring error
Undefined
Incorrect installation
Check installation
P40
No SENSORPROM
®
unit
Install SENSORPROM
®
unit
P44
CT SENSORPROM
®
unit
Replace SENSORPROM
®
unit or re‐
set SENSORPROM
®
unit with MAG
CT transmitter
P49
Protection violation
Switch off MAG 5000/6000/6000I, wait
5 sec. and switch on again.
F61
Defective SENSORPROM
®
unit Replace SENSORPROM
®
unit
F62
Wrong type of SENSOR‐
PROM
®
unit
Replace SENSORPROM
®
unit
F63
Defective SENSORPROM
®
unit Replace SENSORPROM
®
unit
F71
Loss of internal data
Replace MAG 5000/6000/6000 I
Maximum
W30
Flow exceeds 100% of Q
max
.
Check Q
max
(Basic Settings)
W21
Pulse overflow
Volume/pulse too small
Change volume/pulse
Pulse width too large
Change pulse width
Measuring approx.
50%
Missing one electrode connec‐
tion
Check cables
Loss of totalizer data
OK
W20
Initializing error
Reset totalizer manually
##### Signs in display OK
Totalizer roll over
Reset totalizer or increase totalizer unit
Empty pipe error mes‐
sage when Empty
pipe set to off
OK
W31
Empty pipe error
Switch off MAG 5000/6000/6000I, wait
5 sec. and switch on again
10.2
Transmitter check list
If unstable/wrong measurements occur, it is often due to insufficient/wrong earthing or potential
equalization. If earthing connection is OK, check transmitter as described below, and sensor
as described in sensor check lists (see the respective operating instructions).
As all settings are stored in and downloaded from the SENSORPROM
®
, replacement is easily
done and no extra settings need to be made.
Check transmitter
Check transmitter according to the following check table:
Power on transmitter
0
Display light on?
Yes ⇒ 1
No ⇒ 2
1
Flashing error triangles?
Yes ⇒ Check error table
No ⇒ 1.2
1.2
Output and display readings OK?
Yes ⇒ 1.2.1
No ⇒ 1.2.2
Troubleshooting/FAQs
10.2 Transmitter check list
62
SITRANS MAG 6000 I/6000 I Ex de
Operating Instructions, 08/2018,