5. Use select key and change key to change password.
6. Press lock/unlock key to confirm new password.
7. Press top up key two times to exit setup mode.
&KDQJHSDVVZRUG
3DVVZRUG
The factory-set password is 1000, but it can be changed to any value between 1000 and 9999.
Factory setting of password can be re-established as follows:
1. Switch off power supply.
2. While pressing top up key - switch on power supply.
3. Release top up key after 10 sec.
6.4
Changing basic settings
In the basic settings menu it is possible to set the following parameters:
Parameter
Description
Main frequency
Selection of main power supply frequency corresponding to the country in which
the flowmeter is installed (e.g. 60 Hz in America).
Flow direction
Selection of correct flow direction in pipe.
Customer units
Setting of user defined volume and time units.
Q
max
Setting of measuring range, analog outputs and frequency output. Also individ‐
ual dimension-dependent setting of value, decimal point, unit and time.
Q
max
2
Setting of measuring range, analog outputs and frequency output. Also individ‐
ual dimension-dependent setting of value, decimal point, unit and time. This
menu is only visible if chosen as external digital input.
Totalizer
Setting of unit and decimal point.
Low flow cut-off
Setting of a percentage of selected Q
max
. This filters noise in installation reducing
fluctuations in display and all outputs.
Empty pipe cut-off
When set to "On" the alarm will indicate when sensor is running empty. All read‐
ings, display and outputs, will indicate zero.
Velocity unit
Setting of velocity unit per time unit
Error level
Selecting error level at which flowmeter will detect an error.
Note
Totalizer 2 is not visible when batch is selected as digital output.
Commissioning
6.4 Changing basic settings
44
SITRANS MAG 6000 I/6000 I Ex de
Operating Instructions, 08/2018,
A5E02083319-AH