Connecting
5.1 Safety precautions
MAG 6000 I / MAG 6000 I Ex de transmitter
30
Operating Instructions, 04/2016, A5E02083319-AG
5.1
Safety precautions
WARNING
Mains supply from building installation Class II
A fused (max. 16 A) circuit breaker must be installed in close proximity to the equipment
and within easy reach of the operator. It must be marked as the disconnecting device for
the equipment.
WARNING
Wire insulation
The insulation between the connected mains supply and 24 V AC/DC supply for the
flowmeter must at least be rated with double or reinforced insulation at mains voltage.
WARNING
Field wiring installation
Ensure that the National Installation Code of the country in which the devices are installed
is met.
WARNING
Only qualified personnel may carry out work on the electrical connections.
WARNING
Use in hazardous areas
Before opening the terminal box check that:
•
No explosion hazard exists
•
A fire department permission certificate has been issued
•
All connection leads are potential free
Special requirements apply to the location and interconnection of sensor and transmitter.
See "Installation in hazardous area"