Technical data
10
10.1
MAG 8000 water meter
Meter
MAG 8000 Standard
(7ME6810)
MAG 8000 Irrigation
(7ME6880)
MAG 8000 CT
(7ME6820)
Accuracy
Standard calibra‐
tion
± 0.4% of rate ± 2 mm/s ± 0.8% of rate ± 2.5 mm/s
-
Extended calibra‐
tion
± 0.2% of rate ± 2 mm/s
0.4% of rate ± 2.5 mm/s
-
OIML R49
(DN 50 to DN 600
(2" to 24"))
-
-
Class 1 and 2 with turn-
down ratio up to
Q3/Q1 = 400 at Q2/Q1 =
1.6
MI-001
(DN 50 to DN 600
(2" to 24"))
-
-
Class 2 with turn-down ra‐
tio
Q3/Q1 = 250, Q3/Q1 =
200, Q3/Q1 = 160 at Q2/
Q1 = 1.6
NMI 10
-
±2.5% (Q1 ≤ Q ≤ Q4)
-
Media conductivity
Clean water > 20 μs/cm
Temperature
Ambient
−20 to +60 °C
(−4 to +140 °F)
−20 to +60 °C
(−4 to +140 °F)
−20 to +55 °C
(−4 to +131 °F)
Media
0 to 70 °C
(32 to +158 °F)
0 to 70 °C
(32 to +158 °F)
0.1 to 50 °C
(32 to +122 °F)
Storage
−40 to +70 °C
(−22 to +158 °F)
−40 to +70 °C
(−22 to +158 °F)
−40 to +70 °C
(−22 to +158 °F)
Enclosure
IP68/NEMA 6P rating.
Cable glands mounted requires Sylgard potting kit to remain IP68/NEMA 6P,
otherwise IP67/NEMA 4 rating is obtained.
Factory mounted cable provides IP68/NEMA 6P rating
Approvals
Drinking water ap‐
provals
NSF 61 (cold water) USA
WRAS (BS 6920 cold wa‐
ter) UK
ACS Listed France
DVGW W270 Germany
Belgaqua (B)
FM Fire Service (Class
Number 1044)
NSF 61 (cold water) USA
WRAS (BS 6920 cold wa‐
ter) UK
CPA (DN 50 to DN 600)
NSF 61 (cold water) USA
WRAS (BS 6920 cold wa‐
ter) UK
ACS Listed France
DVGW W270 Germany
Belgaqua (B)
FM Fire Service (Class
Number 1044)
Custody transfer
approval
OIML R 49
NMI10 (Australia)
OIML R 49
OIML R 49 MAA
MI-001 (DK-0200-
MI-001-011)
PTB K7.2
SITRANS MAG 8000
Operating Instructions, 11/2018, A5E03071515-AE
91