Coil circuit "Ex e" (Terminal 85,86)
Ui
30 V (70 V peak)
Ii
130 mA
Note
Compact mounted versions
For intrinsically safe data for MAG 3100 Ex compact mounted with MAG 6000 I Ex d, refer to the
Operating Instructions of MAG 6000 I or to certificate number Sira 11ATEX2124X, available
here: Certificates (
http://www.siemens.com/processinstrumentation/certificates
WARNING
With intrinsically safe circuits
If a non-conforming supply unit is used, the "fail-safe" type of protection will no longer be
effective and the approval certification will be invalid.
With intrinsically safe circuits, use only certified meters appropriate for the transmitter.
Temperature specifications for Ex use
Table 2-7
Temperature classifications for MAG 3100 Ex (remote or compact with MAG 6000 I)
Maximum process fluid tempera‐
ture [°C]
Temperature
class
Ambient temperature [°C]
75
T6 (85 °C)
-25 to +60
90
T5 (100 °C)
-25 to +60
125
T4 (135 °C)
-25 to +60
180 (Remote configuration)
T3 (200 °C)
-25 to +60
150 (Compact configuration)
T3 (200 °C)
-25 to +50
For dust protection, the surface temperature is equal to the process fluid temperature plus 5 °C.
Special conditions for safe use
It is required that:
• Electrical connections are in accordance with national requirements.
• Appropriate cable connectors are used for the output circuits:
– Intrinsically safe: blue
– Non-intrinsically safe: black
• Minimum 4 mm
2
cable is to be used for potential equalization
• Cable glands for coil circuit must be Ex e approved (increased safety) and fit the application
by being approved for the cable used as regards size and temperature.
Safety notes
2.4 Installation in hazardous locations
SITRANS FM MAG 3100
Operating Instructions, 12/2021, A5E03005599-AE