6.4.3
Adding the device to the network
It is recommended to configure the FUS080 project in PDM before setting the parameters.
Add device to SIMATIC Modbus network:
1. Select [File → New]
Type in a project name.
2. Right click on your new project, select [Insert New Object → Networks].
3. Right click on your Networks, select [Insert New Object → Communication Network].
4. Click on [Assign Device Type] and select Networks → MODBUS → MODBUS networks →
MODBUS network.
5. Click [OK] and click [OK] again.
6. Right click on MODBUS network and select [Insert New Object → Object]
7. Click on [Assign Device Type] and assign the MODBUS device to SITRANS FUS/E080
[Devices → MODBUS → Sensors → Flow → Ultrasonic → SIEMENS AG → SITRANS FUS/
E080] and click [OK].
Name device according to application requirements (max. 32 characters) and click [OK].
Set up communication parameters for SIMATIC MODBUS network.
8. Select Networks → MODBUS network.
9. Right click on Modbus network and select Object Properties.
10.On the Communication tab, select MODBUS communication to activate IrDA.
Commissioning
6.4 Commissioning via PDM
FUS380/FUE380
52
Operating Instructions, 09/2016, A5E00730100-AB