– Select the Communication tab and configure the communication parameters. The
transmitters default settings are:
- Transmission rate: 19200 baud
- Parity: even
Figure 3-3
Modbus net object properties
– Click OK.
3. Set up the COM interface:
– Select Modbus Networks.
– Right-click on the object name SITRANS FC and select Object Properties.
– Select the Communication tab and configure the Modbus address.
Figure 3-4
Set the Modbus address
– Click OK.
3.7
Configuring a new device
Note
Clicking on Cancel during an upload from device to SIMATIC PDM will result in some
parameters NOT being updated.
Commissioning
3.7 Configuring a new device
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB