Channel 3 output pulse
Table 4-101 Channel 3 output pulse
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9273
Unsigned / 2
Simulation
Enables or disables
simulation of channel 3
output pulses.
0
● 0: Disabled
● 1: Enabled
Read /
write
9278
Float / 4
Simulated value Pulse frequency value
that is output on the
channel when simula‐
tion is enabled.
0.0
[pulses/s]
0.0 - 12500.0
Read /
write
Channel 3 input current
Table 4-102 Channel 3 input current
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
10505
Unsigned / 2
Simulation
Enables or disables
simulation of channel 3
output current.
0
● 0: Disabled
● 1: Enabled
Read /
write
10506
Float / 4
Simulated value Current value that is
output on the channel
when simulation is ena‐
bled.
0
[mA]
0 - 25
Read /
write
Channel 3 discrete input signal
Table 4-103 Channel 3 discrete input signal
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9136
Unsigned / 2
Simulation
Enables or disables
simulation of channel 3
discrete input signal.
0
● 0: Disabled
● 1: Enabled
Read /
write
9137
Unsigned / 2
Simulated value Signal level that that
substitutes the input
signal on the channel
when simulation is ena‐
bled.
0
0, 1
Read /
write
MODBUS commands
4.10 Modbus holding registers tables
FCT030 Modbus (From firmware 4.0)
180
Function Manual, 06/2018, A5E39931813-AB