Channel 4 status output settings
Table 4-46
Channel 3 status output settings
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units register)
Value range /
Setting options
Access
level
9341
Unsigned / 2
Status mode
Select the functionality
for the status output.
0
● 0: Alarm class
● 1: Alarm item
Read /
write
9358
Unsigned / 2
Alarm class
Bit encoded selection
of alarm classes which
impact the status out‐
put. Each diagnostic
event is allocated to an
alarm class. See Alarm
items (Page 145).
Applicable if Status
mode = 0.
0
● Bit 0: Process value
alarm (PA)
● Bit 1: Process value
warning (PW)
● Bit 2: Maintenance
alarm (MA)
● Bit 3: Maintenance
warning (MW)
● Bit 4: Maintenance
required (MR)
● Bit 5: Function check
(FC)
Read /
write
9399
Unsigned / 2
NAMUR status
signals
Bit encoded selection
of NAMUR status sig‐
nals which impacts the
status output. Applica‐
ble if Status mode = 1.
NAMUR status is de‐
rived from Alarm class
(9358).
0
● Bit 0: Out of
specification (PA,
PW)
● Bit 1: Failure (MA)
● Bit 2: Maintenance
required (MR, MD)
● Bit 3: Funtion check
(FC)
Read /
write
9342
Unsigned / 4
Alarm items 1
Bit encoded selection
of alarm items that im‐
pact the output. Mainly
sensor alarms. See
(Page 145). Applicable
if Status mode = 1.
0
Read /
write
9344
Unsigned / 4
Alarm items 2
Bit encoded selection
of alarm items that im‐
pact the output. Mainly
sensor alarms. See
(Page 145). Applicable
if Status mode = 1.
0
Read /
write
9348
Unsigned / 4
Alarm items 4
Bit encoded selection
of alarm items that im‐
pact the output. See
(Page 145). Applicable
if Status mode = 1.
0
Read /
write