Operation
6.4 Parameter menu
SITRANS DA400 for material flow monitoring with protection against explosion
Operating Instructions, 09/2007, A5E00841152-01
51
6.4.3
Setting parameters
Procedure
The procedure for setting a parameter is as follows:
1.
Press the <PAR> button for five seconds to switch to the parameter menu.
"MEnu" and "PARAM" are shown in the middle section of the digital display to the left and
right respectively. "MEnu" flashes. After these 5 seconds, the appearance of the digital
display is as shown below.
2.
Select the parameters with the and buttons.
3.
Set the value of the parameter using the and buttons.
Note
Adjustment of the parameter value takes effect immediately.
Press the <MEAS> button to return to the measured value display. At this point, the
adjusted parameters are saved to ensure operation even in case of power failure.
If the parameter lock is effective, "noPA" appears in the digital display when you attempt
to make the adjustment and it is not possible to adjust the parameter.
6.4.4
Displaying the software version
Introduction
The software version has the format "xx.yy.zz" (e.g., "3.00.01").
Procedure
When the parameter P.0 is selected, "xx.yy" (e.g., "3.00") appears in the digital display.
By simultaneously pressing the and buttons, ". .zz" (e.g. ". .01") appears in the digital
display.