Operation
6.3 Measuring menu
SITRANS DA400 for material flow monitoring with protection against explosion
46
Operating Instructions, 09/2007, A5E00841152-01
6.3.5.2
Analog input
Introduction
You may use external transmitters with the following analog output signals:
●
Analog signal 0-20 mA
●
Analog signal 4-20 mA
Condition
The measurement channel must be configured as an analog input. The measurement
channel is configured as an analog input if the parameter P.26 to P.29 associated with the
measurement channel is set to the value "0-20", "4-20", "20-0" or "20-4".
Elements of the digital display with analog inputs
Figure 6-8
Measuring menu digital display, analog input
➀
Standardized measured value; flashes if alarm received. The measuring range selected with
the parameter 26 to 29 is standardized to 0 to 100%.
②
Limit value exceeded.
③
Summation alarm received from acoustic channels.
④
Number and name of the measurement channel
⑤
Associated limit value (here, parameter "P.30/ALI1").
See also