![Siemens SITRANS AW 7MP3112 Series Operating Instructions Manual Download Page 31](http://html.mh-extra.com/html/siemens/sitrans-aw-7mp3112-series/sitrans-aw-7mp3112-series_operating-instructions-manual_1265484031.webp)
Connecting
6
6.1
Electrical installation
6.1.1
Cabling when the adapter is mounted directly on the field device
Requirement
For the electrical installation of the WirelessHART adapter, you require a slotted screwdriver
with a blade 2.5 mm wide.
Cable specification
NOTICE
Use the correct cable
● If the adapter is mounted directly, use the two-wire cable with a length of 38 cm supplied
with the product.
● If you install the adapter away from the field device, you can use commercially available
installation cable.
● If strong electromagnetic interference can be expected, for example from machines or
wireless devices, we recommend that you use a shielded cable.
● Contact the shield only to the ground connector.
Cabling when the adapter is mounted directly on the field device
If the adapter is installed directly on the field device, follow these steps:
1. Open the housing of the WirelessHART adapter.
2. Insert the cable through the mounting collar.
3. Connect the cable as described in the section "Wiring diagrams" (Page 33) to the
appropriate terminals of the WirelessHART adapter.
4. Wire up the field device according to the operating instructions of your field device.
WirelessHART Adapter SITRANS AW200