Operation
5.6 Parameter descriptions
SITRANS TF280 WirelessHART
Operating Instructions, 10/2010, A5E02619566-02
55
"4.1.4 Transmission rate"
Factory setting:
60 s
Setting range:
8 to 3600 s
Purpose:
Set transmission rate.
Description:
Setting of time intervals at which the transmitter sends measured values.
Increase or decrease the parameter value by pressing the ↑ or ↓ key.
Corresponds to parameter "1.4 Transmission rate" (Page 44) .
"4.1.5 Disconnect network"
CAUTION
Personal injury and damage to property
Activation of this function during operation interrupts the connection between the transmitter
or router and the network. Depending on the topology, this may result in failure of the
wireless HART network and also personal injury and/or damage to property. Therefore:
Avoid inadvertent operations:
Make sure that the password input is always activated.
Check on the gateway whether the device can be removed from the network without
resulting in a failure or danger.
Requirements:
Removal of device from the wireless HART network without danger is
guaranteed
PIN input function is active
Factory setting:
-
Setting range:
START
Purpose:
Interrupt communication of device with other network stations
Description:
Preparation for removal of device. The network and address parameters are
not deleted. Through activation of the parameter "4.1.3 Connect network"
(Page 54) the device reestablishes the connection.
Start this function by pressing the M key. Then: Execution depends on input
of PIN!
See also