Functions
7.8 Analog Input Setup
FUE1010 IP65 NEMA 4X
Operating Instructions, 12/2014, A5E03086491-AC
121
CE Method
The ultrasonic energy flow meters can be configured to provide an Energy Efficiency output.
Modifications were implemented using the standard analog input spanning methods in an
effort to simplify operator monitoring of air conditioning efficiency data. These changes allow
the flow meter to calculate chiller efficiency. The flow meter calculates chiller or heating
efficiency through use of an available analog input, which can be assigned to represent
power consumption (kW).
Note
Refer to www.EngineeringToolBox.com (
KW/ton
Cooling Load in kW/ton - Commonly used for large commercial and industrial air-
conditioning, heat pump and refrigeration systems. KW/ton is defined as the ratio of the rate
of energy consumption in kW to the rate of heat removal in tons at the rated condition. The
lower the kW/ton the more efficient the system.
kW/ton = P
c
/ E
r
where: P
c
= energy consumption (kW)
E
r
= heat removed (ton)
COP
Coefficient of Performance - COP is the basic unit less the parameter used to report the
efficiency of refrigerant based systems. COP is the ratio between useful energy acquired and
energy applied.
COP = E
u
/ E
a
Where: E
u
= useful energy acquired
E
a
= energy applied.
COP can be used to define both cooling efficiency or heating efficiency as with a heat pump.
●
For cooling, COP is defined as the ratio of rate of heat removal to the rate of energy input
to the compressor.
●
For heating, COP is defined as the ratio of the rate of heat delivered to the rate of energy
input to the compressor.
COP can be used to define the efficiency at a single standard or non-standard condition or a
weighted average seasonal condition. The term may or may not include the energy
consumption or auxiliary systems such as indoor or outdoor fans, chilled water pumps, or
cooling tower systems. For purposed of comparison the higher the COP the more efficient
the system.
COP can be treated as an efficiency where COP of 2.00 = 200% efficient. For unitary heat
pumps, ratings at two standard outdoor temperatures of 47°F and 17°F (8.3°C and -8.3°C)
are typically used.
Summary of Contents for SITRANS 7ME3500
Page 2: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 251: ......
Page 252: ......
Page 253: ......
Page 254: ...21614 C 1011NFPS 7 ...
Page 255: ...1011NFPS 7 C 21614 ...
Page 256: ...1011NFPS 7 C 21614 ...
Page 257: ...21614 C 1011NFPS 7 ...
Page 258: ......
Page 259: ......
Page 260: ......
Page 261: ......
Page 262: ......
Page 263: ...21614 C ...
Page 264: ......
Page 265: ......
Page 266: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 267: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 268: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 269: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 270: ......
Page 271: ......
Page 272: ......
Page 273: ......
Page 274: ......
Page 275: ......
Page 276: ...21614 C STEP 4 BAND LENGTH TABLE PERMANENT INSTALLATION SERVICE NOTE STEP 2 STEP 3 STEP 1 ...
Page 277: ......
Page 278: ......
Page 279: ......
Page 280: ......
Page 282: ......
Page 290: ...Glossary FUE1010 IP65 NEMA 4X 216 Operating Instructions 12 2014 A5E03086491 AC ...
Page 294: ...Index FUE1010 IP65 NEMA 4X 220 Operating Instructions 12 2014 A5E03086491 AC ...
Page 295: ......