![Siemens SITOP PSU100S Operating Instructions Manual Download Page 52](http://html.mh-extra.com/html/siemens/sitop-psu100s/sitop-psu100s_operating-instructions-manual_382596052.webp)
Technical data
6.7 Mechanical system
SITOP PSU100S
52
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6.7
Mechanical system
6EP1332-2BA20
6EP1333-2BA20
6EP1322-2BA00
6EP1334-2BA20
6EP1323-2BA00
6EP1336-2BA10
Connection system
Screw-type terminal
Connections / line
supply
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² solid/finely stranded
L1, N, PE: 1 screw
terminal each for 0.2 ...
4 mm² solid/finely
stranded
Connections / output
+, -: 2 screw terminals each for 0.5 ... 2.5 mm²
+, -: 2 screw terminals
each for 0.2 ... 4 mm²
Connections / auxiliary
contacts
Signals: 2 screw terminals for 0.5 mm ... 2.5 mm²
13, 14 (signal): 1
screw terminal each
for 0.14 ... 1.5 mm²
Width of the housing
32.5 mm
50 mm
70 mm
115 mm
Height of the housing 125 mm
125 mm
125 mm
145 mm
Depth of the housing
120 mm
120 mm
120 mm
150 mm
Installation width
32.5 mm
50 mm
70 mm
120 mm
Mounting height
225 mm
225 mm
225 mm
245 mm
Weight, approx.
0.32 kg
0.5 kg
0.8 kg
2.4 kg
Product feature of the
housing / housing that
can be lined up next to
one another
Yes
Type of mounting /
panel mounting
No
Type of mounting / rail
mounting
Yes
Type of mounting / S7-
300 rail mounting
No
Mounting
Can be snapped onto standard EN 60715 35x7,5/15 mounting rails