Operator control at the device
3.6 ELECTRONIC SHUTDOWN and CONSTANT CURRENT operating modes
PSU8600power supply systems
64
Manual, 04.2016, A5E35883207-7-76
3.6
ELECTRONIC SHUTDOWN and CONSTANT CURRENT operating
modes
Two overload responses can be defined for output 4:
●
In the ELECTRONIC SHUTDOWN mode, overload is permitted for a defined time. The
output is electronically shut down after the limit value has been exceeded (see Overload
shutdown and carrying out a reset (Page 56)).
●
In the CONSTANT CURRENT mode, an overload current is continually permissible (U/I
curve) according to a defined characteristic. The overload current is limited to a maximum
of 150 % of the setting value of the current potentiometer for a duration of 5 seconds
(LED "ON/OFF/RST" of output 4 quickly flashes green); the current is then limited to
100 % of the setting value (LED "ON/OFF/RST" of output 4 slowly flashes green) as long
as there is an overload condition.
Note
How the system responds to overload may only be switched over when the power supply
system is in a no-voltage state.
The switchover is made at the selector switch (see operator controls) with the designation
"UI-4"
⑥
.
When delivered, DIP switch "UI-4" is in position "OFF" (mode ELECTRONIC SHUTDOWN).