Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
200
Manual, 04.2016, A5E35883207-7-76
Operating state output 1... 4 (Channel1...4 operating state)
The status messages of an output are listed in the table below. The data applies to outputs 1
to 4.
Status message
Description
0 = ManualOff
Output switched off manually (button): The output was manually switched off using the
button on the device. The device can only be switched on manually using the button on the
device.
1 = RemoteOff
Output switched off (PROFINET/IE): The output was remotely switched off via
PROFINET/IE.
2 = BufferOff
Output switched off (prioritization output 1): The output was switched off during buffer oper-
ation.
3 = OverLoadOff
Output switched off (overload): Inadmissible overload at the output has occurred. The out-
put was switched off.
4 = ReadyForRestart
Output ready for reset (reset): Output is ready to be switched on again after automatic over-
load shutdown.
5 = ErrorOff
Output switched off (fault).
6 = Boot
Output switched off (powering up).
7 = Running
Output switched on (normal operation)
8 = OverLoad
Output in overload operation: The output current is above the specified response threshold,
but still within the permissible overload profile.
9 = Limit
Output current limited to the response threshold: The output is in the overload mode. The
output current is limited to the configured response threshold.
10 = Overloaded
AfterSystemOverload
Output in overload operation (system overload).
11 = LimitAfter
SystemOverload
Output current limited (system overload).
7.6.1.5
Operating states SITOP BUF8600
Operating state of the buffer module (buffer operating state)
Status message
Description
0 = Off
Buffer component is in the "Off" operating state.
1 = Boot
Buffer component is powering up.
2 = Full
Complete buffer readiness: The energy storage device of the buffer component is fully
charged (normal operation).
3 = Buffering
The buffer component is operating in the buffer mode: The power supply system is supplied
via the buffer component(s).
4 = ErrorOff
Shutdown after an error: A fault/error has occurred when operating the buffer component.
The buffer component is not operational and must be restarted by switching off the supply
voltage and switching it on again.
5 = NotFully
ChargedReady
Ready for buffer operation as the energy storage device of the buffer module has been
sufficiently charged.
6 = NotFully
ChargedNotReady
Not ready for buffer operation as the energy storage device of the buffer module has not
been sufficiently charged and is presently being charged.
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...