Engineering and remote access
7.3 SIMATIC STEP 7 in the TIA Portal
PSU8600power supply systems
130
Manual, 04.2016, A5E35883207-7-76
7.3.6.2
Parameterizing the basic unit
The procedure is the same for all parameters. The individual parameters and their possible
values are described in the following sections.
Preconditions
●
The SITOP PSU8600 was integrated in the opened project
Procedure
1.
Select the SITOP PSU8600 in the Device view.
2.
In the inspector window, select "Properties > General > Device configuration".
Entries for parameterization are provided in the navigation area.
Parameters, general
Parameter
Value range
Default setting
Prioritized buffering of out-
put 1
Yes/no
No
Parallel switch-on output 1
and output 2
Yes/no
No
Parallel switch-on output 3
and output 4
Yes/no
No
Prewarning threshold
0 - 100 %
90 %
System start characteristics
•
No on delay
•
25 ms on delay
•
100 ms on delay
•
Load-optimized on delay
•
Variable on delay
No on delay