
3RT1/3RH1 contactors
SIRIUS System Manual
GWA 4NEB 430 0999-02b
3-35
Kits
The following table shows you the components of the kit for the contactor
combination for reversing in frame size S00 and explains how to put it
together:
Table 3-16: Assembling the contactor combination for reversing (frame size S00)
Electrical interlock
Note:
Contactors with an NC contact in the basic unit (3RT101.) are required for
the electrical interlock.
Drawing: frame size S00
Step
Procedure
1/2/3
Mount the mechanical inter-
lock between the two contac-
tors.
4/5
Press the two connecting clips
from above and below onto the
two contactors.
6
Attach the wiring modules to
connect the main conducting
paths and to electrically inter-
lock the two contactors
(3RT10.1). Make sure that the
wiring modules are flush with
the contactor at the side.
5
4
1
3
2
6
6