Appendix
A.1 Process data and data sets
SIRIUS ACT 3SU1 pushbuttons and signaling devices
576
System Manual, 08/2018, A5E03457306020A/RS-AK/010
Data set
Name
Access Value
Length
(bytes)
Index
(dec)
Index
(hex)
Subindex
supported
92
5C
Yes
Diagnostics - data set 92
r
—
20
94
5E
Yes
Diagnostics - data set 94
r
—
22
131
83
Yes
Parameters - data set 131
r / w —
20
A.1.1.2
IO-Link communication parameters
Parameter Page 1 - IO-Link communication parameters
Table A- 2
Parameter Page 1
Address
Parameter name
Access
Description
0x00
Master Command
w
—
0x01
Master Cycle Time
r / w
—
0x02
Min. Cycle Time
r
FW 1.4.0 or FW 2.0.0 in compatibility mode: 0x6e
FW 2.0.0: 0x32
0x03
M-Sequence Capability
r
0x11
0x04
IO-Link Revision ID
r / w
0x11
0x05
Process data IN
r
FW 1.4.0 or FW 2.0.0 in compatibility mode: 0x50
FW 2.0.0: 0x10
0x06
Process data OUT
r
0x00
0x07
Vendor ID 1
r
0x00
0x08
Vendor ID 2
r
0x2a
0x09
Device ID 1
r / w
0x0c
0x0A
Device ID 2
r / w
0x03
0x0B
Device ID 3
r / w
FW 1.4.0 or FW 2.0.0 in compatibility mode: 0x01
FW 2.0.0: 0x02
0x0C
Function ID 1
r
0x00
0x0D
Function ID 2
r
0x00
0x0E
Reserved
r
—
0x0F
System Command
w
—