SIRIUS
Extension Device
3TK2830
DIN EN 60947-5-1 (08.00)
Operating Instructions
Order No.: 3ZX1012-0TK28-3CA1
English
2
Read and understand these instructions before installing, operating, or maintai-
ning the equipment.
Reliable functioning of the equipment is only ensured with certified components.
The devices must be installed in a switchgear cabinet with the IP32, IP43 or
IP54 degree of protection, depending on the ambient conditions.
The products described herein are designed to be components of a custom-ized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, actuators and signaling components. It
is the responsibility of each company to conduct its own evaluation of the effec-
tiveness of the safety system with the help of suit-ably trained persons. Sie-
mens AG and its subsidiaries and affiliates (collectively "Siemens") are not in a
position to evaluate all of the characteristics of a given machine or product or
machine not designed by Siemens.
Siemens accepts no liability for any recommendation that may be implied or sta-
ted herein. The warranty contained in the contract of sale by Siemens is the sole
warranty of Siemens. Any statements contained herein do not create new war-
ranties or modify existing ones.
The 3TK2830 is used to expand the enabling circuits. You can combine it with
any 3TK28 basic unit. The maximum achievable safety category according to
DIN EN 954-1 is the category of the basic unit, providing the external circuit
(connection between the basic unit and the expansion unit) is fail-safe.
The 3TK2830 has four safe enabling circuits as NO circuits and one positively-
driven NC circuit. Two LEDs indicate the operating condition.
The 3TK2830 can be controlled via any enabling circuit in the basic unit. NC cir-
cuit 51/52 of the 3TK2830 is looped into the feedback circuit of the basic unit.
The internal circuit is functionally tested by the upstream basic unit.
Be sure to fit the specified fuses. Otherwise safe interruption
in the event of a fault cannot be guaranteed.
For further data and accessories see Catalog.
DANGER
Hazardous voltage.
Will cause death or serious injury.
Disconnect power before working
on equipment.
IMPORTANT NOTICE
Application
Functions and connections
Terminal
assignments
Operating
voltage
A1
A2
L/+
N/–
Outputs
13, 14
23, 24
33, 34
43, 44
Enabling circuit 1 (NO contact)
Enabling circuit 2 (NO contact)
Enabling circuit 3 (NO contact)
Enabling circuit 4 (NO contact)
Feedback
circuit
51, 52
3TK2830 monitoring (NC contact)
Cable lengths
3TK2830- .CB30:
max. 1000 m
.AJ20:
max. 300 m
.AL20:
max. 80 m
Figures
Fig. I:
Dimension drawings (dimensions in mm)
Fig. II:
Installation
Fig. III:
Internal circuit:
¿
Power pack,
À
Control logic,
Á
Channel 1,
Â
Channel 2
Fig. IV:
Guard door monitoring, category 4 per DIN EN 954-1
Fig. V:
EMERGENCY STOP, category 4 per DIN EN 954-1
Fig. VI:
EMERGENCY STOP with time delay
!
Operating states
LED
Operation
Channel 1
Channel 2
PS
Enabling circuits
ON
Closed
Open
Faults
• Relay fusion-welded
• Defect in electronics
• Motor contactor fusion-welded
• No supply voltage
Technical data
Permissible ambient temperature T
u
- Operation
- Storage
–
25 to +60 °C
–
40 to +80 °C
Degree of protection to EN 60 529
IP40, IP20 at terminals
Rated insulation voltage U
i
300 V
Rated impulse withstand voltage U
imp
4 kV
Rated control supply voltage U
s
24 V AC/DC, 115 V AC, 230 V AC
Rated power
2 W
DC operating range
0.85 to 1.2 x U
s
AC operating range 115 V / 230 V
0.85 to 1.1 x U
s
AC operating range 24 V
0.80 to 1.1 x U
s
Shock resistance (half-sine) as per IEC 60068
8
g
/10 ms
Weight
max. 0,26 kg
Recovery time 3TK2830-.CB30
50 ms
Recovery time 3TK2830-.A.20
100 ms
Release time 3TK2830-.CB30
max. 25 ms
Release time 3TK2830-.A.20
max. 80 ms
Response time 3TK2830-.CB30
Response time 3TK2830-.A.20
max. 30 ms
max. 200 ms
Utilization
category
per IEC 60947-5-1
Rated operational
voltage U
e
/ (V)
Rated operational
current I
e
/ (A)
with all enabling circuits loaded
40 °C 50 °C
60 °C
70 °C
AC-15
230
5
4
3.5
3
DC-13
24 5
4
3.5
3
115 0.2
0.2
0.2
0.2
230 0.1
0.1
0.1
0.1
Continuous current I
th
5
4
3.5
3
Short-circuit
protection for
release circuit
Fuse links
DIAZED
Duty class
gL(gG)
quick response
6 A
10 A