![Siemens SIRIUS 3RW5 series Equipment Manual Download Page 23](http://html.mh-extra.com/html/siemens/sirius-3rw5-series/sirius-3rw5-series_equipment-manual_1265469023.webp)
-
Monitoring
Diagnostics
Control
Parameterization
Web server
3)
✓
✓
✓
4)
-
OPC UA server
3)
✓
✓
-
-
1)
Via local interface on 3RW5 HMI High Feature or via 3RW5 communication module
2)
Dependent on the 3RW5 soft starter
3)
Only via 3RW5 PROFINET High Feature communication module
4)
Login necessary with "Operator personnel" or "Maintenance personnel" user role. For more information on user account
management, refer to the 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual.
Possible number of applications per access path
The following number of applications are simultaneously possible via the 3RW5 PROFINET
communication module for each access path:
Access path
3RW5 PROFINET communication
module
Standard
High Feature
Programmable logic controller (e.g. SIMATIC S7‑1500)
1
1
SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
1
4
1)
Web client
-
5
2), 3)
OPC UA client
-
2
2), 3)
1)
3RW5 PROFINET High Feature communication module from firmware version V1.1 (previously only one
application was possible)
2)
3RW5 PROFINET High Feature communication module from firmware version V2.0
3)
Soft starter 3RW55 with firmware version V2.1.1 or higher or soft starter 3RW55 Failsafe with firmware
version V1.1.0 or higher
Description
3.4 Access options for the 3RW5 soft starters
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
23