PROFIBUS DP communication module
9.4 Activating the PROFIBUS DP communication module (fieldbus interface) and setting the station address
3RW44 soft starters
156
Manual, 03/2017, NEB535219502000/RS-AB/008
9.4
Activating the PROFIBUS DP communication module (fieldbus
interface) and setting the station address
9.4.1
Introduction
Activate the PROFIBUS DP communication module ("Fieldbus" device function) and set the
station address either via the display or the device interface using the "Soft Starter ES
Premium" or "Soft Starter ES + SP1" software.
Note
After the communication module has been activated, the default control priority automatically
switches from the inputs to the PROFIBUS DP communication module.
If an input with the "Manual mode local" function is active, the control priority does not
change (refer to chapter Parameterizing the inputs (Page 89)).
The soft starters are pre-set to station address 126 as the factory default.