SIRIUS 3RR2 current monitoring relays
8.10 Technical data
SIRIUS Innovations
734
System Manual, 01/2011, A8E56203870002-03
8.10.1.2
Monitoring functions
Table 8- 15 Monitoring functions of 3RR2 current monitoring relays
Feature
Benefit
3RR21 Basic,
analog setting
3RR22 Standard,
digital setting
Current overshoot
Provides optimum current-dependent
protection of loads against impermissibly high
temperature rise due to overload
Enables detection of filter blockages or pumps
working against closed slide valves
Enables conclusions to be drawn about wear,
poor lubrication or other phenomena relevant
to maintenance
✓ (2-phase)
✓ (3-phase)
Current undershoot
Enables detection of overload due to a slipping
or torn belt
Ensures that pumps are protected against
running dry
Straightforward function monitoring of resistive
loads such as heaters
Permits energy savings to be made through
monitoring of no-load operation
✓ (2-phase)
✓ (3-phase)
Apparent current monitoring
Sensitive current monitoring specifically in a
motor's rated and upper torque range
✓
✓
Active current monitoring
Optimum current monitoring over a motor's
entire torque range thanks to the patented
combination of power factor and apparent
current monitoring
-
✓ (selectable)
Range monitoring
Simultaneous monitoring for current overshoot
and undershoot with a single device
✓ (2-phase)
✓ (3-phase)
Phase failure, wire break
Minimizes the temperature rise of the three-
phase motor in the event of a phase failure
thanks to immediate disconnection
Prevents hoisting gear from operating with half
payload
✓ (2-phase)
✓ (3-phase)
Phase sequence error
Prevents motors, pumps or compressors
starting up in the wrong direction of rotation
-
✓ (selectable)
Internal ground-fault
detection (fault current
monitoring)
Provides optimum protection of loads in the
event of high-impedance faults to ground
caused by moisture, condensation, damaged
insulation, etc.
Eliminates the need for additional special
equipemnt
Saves space in the control cabinet
Reduces wiring outlay and costs
-
✓ (selectable)
Blocking current monitoring
Prevents temperature rise of the three-phase
motor in the event of blocking during operation
thanks to direct disconnection
Minimizes the mechanical loading of the
system by functioning as an electronic shear
pin
-
✓ (selectable)