5.10.2
3RU21
5.10.2.1
General technical data
Table 5- 38 General technical data for 3RU21 overload relays
Type
3RU21 16
3RU21 26
Size
S00
S0
Width
45 mm
45 mm
Tripping in the event of
Overload and phase failure
Tripping class according to IEC/EN 60947-4-
1
CLASS
10
Phase loss sensitivity
Yes
Overload warning
No
Resetting and recovery
Reset options following tripping
Manual, automatic, and remote RESET
1)
Recovery time
- Automatic RESET
min
Depending on the level of the tripping current and the tripping
characteristic curve
- Manual RESET
min
Depending on the level of the tripping current and the tripping
characteristic curve
- Remote RESET
min
Depending on the level of the tripping current and the tripping
characteristic curve
Equipment
Display of operating state on device
Yes, by means of TEST function/switch position indicator slide
TEST function
Yes
RESET button
Yes
STOP button
Yes
Safe operation of motors with
"increased safety" explosion protection type
EC type examination certificate number
according to Directive 94/9/EC
On request
Ambient temperature
Storage/transport
°C
-55 ... + 80
Operation
°C
-40 ... + 70
Temperature compensation
°C
Up to 60
Permissible rated current at internal cubicle temperature
- Up to 60 °C
%
100 (current reduction is required above +60 °C)
- 60 °C to 70 °C
%
87
Repeat terminals
Coil repeat terminal
Yes
Not required
Auxiliary switch repeat terminal
Yes
Not required