SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
280
System Manual, 01/2011, A8E56203870002-03
2.8.5.2
General data - OFF-delay device 3RT2916-2B.
Table 2- 120 OFF-delay device 3RT2916-2B.
3RT2916-2BE01
3RT2916-2BK01
3RT2916-2BL01
Versions
OFF-delay device
Connectable contactor sizes
Notice! Only contactors and contactor relays with DC
drive can be connected!
DC supply
S00/S0
S00/S0
S00/S0
AC supply
---
S00/S0
S00/S0
Type
3RT20..-1BB4.
3RH2...-1BB40
3RT201.-1BF4.
3RT202.-1BF4.
3RH2...-1BF40
3RT201.-1BM4./
1BP4.
3RT202.-1BM4./
1BP4.
3RH2...-1BM40/
1BP40
Permissible mounting
position
r
r
Rated control supply voltage U
S
24 (DC)
110 (DC)
220/230 (UC)
Operating range
V
0.9 to 1.1 x U
S
Rated frequency(cies)
with AC supply
f
Hz ±5%
---
50 / 60
Ambient temperature, permissible:
Operation
- Side-by-side mounting
without clearance
T
u
°C -25 … +50
- Side-by-side mounting with
5 mm clearance
T
u
°C -25 … +60
Storage
T
u
°C -40 … +80
OFF-delay
1)
(minimum times at U
sp
= 0.9 x U
S
, T
sp
= 20 °C)
Note:
In practice the mean value is equal to 1.5 times the minimum time.
S00
t
OFF
>
ms
200
100
500
S0
t
OFF
>
ms
100
80
300
Installed capacitance C
3RT2916-2B.01
μF
2000
68
68
Capacitor voltage
V
35
180
350
ON-delay
(maximum at U
sp
= 0.9 x U
S
, T
sp
= 20 °C)
Note:
Total ON-delay = contactor ON time + t
ON
S00
t
ON
>
ms
10
60
200
S0
t
ON
>
ms
10
80
250