![Siemens SIRIUS 3RH Series System Manual Download Page 272](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139272.webp)
SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
272
System Manual, 01/2011, A8E56203870002-03
Table 2- 112 Contact reliability of 3RH2 contactor relays
Type
3RH2
Size
S00
Contact reliability
Contact reliability at 17 V, 1 mA acc. to DIN EN 60947-5-4
Frequency of contact faults < 10-8, i.e. < 1 error per
100 million operating cycles
2.8.4.2
General data, rated data (CSA and UL), and data relating to short-circuit protection for
3RH2. contactor relays
Table 2- 113 General data – 3RH2. contactor relays
Type
3RH21, 3RH22
3R24
Size
S00
General data
Basic device
30 million
5 million
Basic device with snap-
on auxiliary switch block
10 million
Mechanical durability
Solid-state compatible
auxiliary switch block
Opera
ting
cycles
5 million
Rated insulation voltage U
i
(pollution degree 3)
V
690
Rated impulse withstand voltage U
imp
kV
6
Protective separation between coil and contacts in basic
device acc. to DIN EN 60947-1, Annex N
V
400
Operation
°C
-25 … + 60
Permissible ambient
temperature
Storage
°C
-55 … + 80
Degree of protection to EN 60947-1, Annex C
IP20, drive system IP40
Touch protection acc. to DIN EN 50274
Finger-safe
Shock resistance
g/ms
7.3/5 and 4.7/10
Rectangular pulse
AC operation/DC operation
g/ms
> 10/5 and > 5/10
g/ms
11.4/5 and 7.3/10
Sine pulse
AC operation/DC operation
g/ms
> 15/5 and > 8/10