![Siemens SIRIUS 3RH Series System Manual Download Page 263](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139263.webp)
SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
263
2.8.2.3
General data, short-circuit protection for contactors without overload relay and
actuation (3RT251. and 3RT252. contactors)
Table 2- 99 General data - 3RT251. and 3RT252. contactors
Type
3RT2516
3RT2517
3RT2518
3RT2526
Size
S00
S0
General data
Permissible mounting position
1)
Mechanical durability
Opera-
ting
cycles
30 million
10 million
Electrical durability
Opera-
ting
cycles
Approx. 0.5 million
Rated insulation voltage U
i
(pollution degree 3)
V
690
Operation
°C
-25 … + 60
Permissible ambient
temperature
Storage
°C
-55 … + 80
Degree of protection to EN 60947-1, Annex C
IP20
IP20
(terminal
compartment
IP00)
Touch protection acc. to DIN EN 50274
Finger-safe
1)
Corresponding to the relevant 3-pole 3RT2. contactors.
Table 2- 100 Short-circuit protection for contactors without overload relay (3RT251. and 3RT252. contactors)
Type
3RT2516
3RT2517
3RT2518
3RT2526
Size
S00
S0
Short-circuit protection for contactors without overload relay
Main circuit
Fuse links, gL/gG
Type of coordination
"1"
A 35
63
NH 3NA, DIAZED 5SB,
NEOZED 5SE
Type of coordination
"2"
A 20
35
Acc. to
IEC 60947-4-1/DIN EN 60947-4-1
Weld-free
V 10
16