96
43-TV-25-35 GLO Iss.4 Dec 06 UK
A5E01001767-04
Power up
In this menu there is a button for each slot for Cold Junction Calibration. Calibration is per-
formed per slot/card.
• Select the desired slot button. If a CJC connector is not fitted a message box will
appear.
• The CJC temperature reading is displayed in the
CJ Temp
column.
• If the known temperature is different to the recorder’s reading an Offset can be entered
to make an adjustment to future values. The Cold Junction temperature should be
measured at the point where the thermocouple is connected in the terminal block.
Ensure the measured temperature is accurate to within 0.1
°
C.
• Enter the difference between the
CJ Temp
on the recorder and the measured reading
as the
Offset Value.
The offset is added to all future readings and displayed in the
Cal-
ibrated CJ Temp
column.
• The
Measured Temp
column will display the actual temperature using the
Calibrated
CJC Temp,
on channels with T/C fitted. For more details of how a thermocouple works,
“Appendix C: Thermocouple Connections” on page 247.
• Select the tick box to go back and the Finish button to Commit, Discard or Commit
Later.
Demo Traces
(Configure > Setup > Edit Setup> General > Factory > Demo Traces)
A set of demo traces available for demonstration or simulation purposes when no Analogue
cards are fitted.
Options for each demo trace are:
•
No Simulation -
Demo traces are deactivated and no simulation traces are
available.
•
Simulate if board not fitted -
Simulation is activated when an Analogue In card is
not fitted in one of the top two slot positions.
Reset Setup
(Configure > Setup > Edit Setup> General > Factory > Reset Setup)
This will remove the current setup from the recorder and return to the default setup. When
you select this button the “
Reset Setup Warning
” box will appear with a message:
“Are you
sure you want to clear your current setup?
This is irreversible and will restart the re-
corder”.
Select OK to reset the setup or Cancel to ignore and return to the Factory menu.
Delete All Data
(Configure > Setup > Edit Setup> General > Factory > Delete All Data)
This button will delete all data from the internal memory. When you select this button the
“
Reset Data Warning
” box will appear with a message: “
This will delete ALL log and
chart data, taking approx 80 seconds to complete and will restart the recorder during
the process
”. 80 seconds is an approximate time depending on the size of the internal
memory. Select OK to proceed. This is an irreversible procedure.
Summary of Contents for SIREC D200
Page 2: ......
Page 176: ...170 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Firmware Credit System ...
Page 222: ...216 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 238: ...232 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 258: ...252 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 270: ...264 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 274: ...268 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Modbus Function Codes ...
Page 284: ...278 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 285: ......