Functions
2.1 General
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
55
2.1.3.3
Settings
2.1.3.4
Information List
2.1.4
General Protection Data (Power System Data 2)
The general protection data (
P.System Data 2
) include settings associated with all functions rather than a
specific protection, monitoring or control function. In contrast to the
P.System Data 1
as discussed before,
these can be changed over with the setting groups and can be configured via the operator panel of the device.
To ensure uniform conversion factors of measured values for WEB-Monitor and control centres, the setting of
all operational rated values of the parameter groups under
P.System Data 2
should be identical.
2.1.4.1
Setting Notes
Rated values of protected lines
The information under this margin heading only apply if no power transformer is located within the protected
zone (device version without transformer option or address
143
TRANSFORMER
set to
NO
, Section 2.1.1.3).
With address
1103
FullScaleVolt.
you inform the device on the primary rated voltage (phase-to-phase) of
the equipment to be protected. This setting influences the displays of the operational measured values in %.
The primary rated current (address
1104
FullScaleCurr.
) is that of the protected object. For cables the
thermal continuous current-loading capacity can be used as a basis. For overhead lines the nominal current is
usually not defined. Here it is advisable to select the rated current of the current transformers (as in address
205
CT PRIMARY
, Section 2.1.2.1). If the current transformers have different rated currents at the ends of the
protected object, set the highest rated current value for all ends.
Addr.
Parameter
Setting Options
Default Setting
Comments
301
ACTIVE GROUP
Group A
Group B
Group C
Group D
Group A
Active Setting Group is
302
CHANGE
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another Setting Group
No.
Information
Type of In-
formation
Comments
-
P-GrpA act
IntSP
Setting Group A is active
-
P-GrpB act
IntSP
Setting Group B is active
-
P-GrpC act
IntSP
Setting Group C is active
-
P-GrpD act
IntSP
Setting Group D is active
7
>Set Group Bit0
SP
>Setting Group Select Bit 0
8
>Set Group Bit1
SP
>Setting Group Select Bit 1