Functions
2.25 Function Control and Circuit Breaker Test
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
458
Table 2-20
Circuit breaker test programs
Figure 2-228
TRIP-CLOSE test cycle
2.25.2.2 Information List
Serial
No.
Test Programs
Circuit
Breaker
Output Indications (No.)
1
1-pole TRIP/CLOSE-cycle phase L1
CB 1
CB1-TESTtrip L1 (7325)
2
1-pole TRIP/CLOSE-cycle phase L2
CB1-TESTtrip L2 (7326)
3
1-pole TRIP/CLOSE-cycle phase L3
CB1-TESTtrip L3 (7327)
4
3-pole TRIP/CLOSE-cycle
CB1-TESTtrip 123 (7328)
Associated close command
CB1-TEST CLOSE (7329)
No.
Information
Type of In-
formation
Comments
-
CB1tst L1
-
CB1-TEST trip/close - Only L1
-
CB1tst L2
-
CB1-TEST trip/close - Only L2
-
CB1tst L3
-
CB1-TEST trip/close - Only L3
-
CB1tst 123
-
CB1-TEST trip/close Phases L123
7325
CB1-TESTtrip L1
OUT
CB1-TEST TRIP command - Only L1
7326
CB1-TESTtrip L2
OUT
CB1-TEST TRIP command - Only L2
7327
CB1-TESTtrip L3
OUT
CB1-TEST TRIP command - Only L3
7328
CB1-TESTtrip123
OUT
CB1-TEST TRIP command L123
7329
CB1-TEST close
OUT
CB1-TEST CLOSE command
7345
CB-TEST running
OUT
CB-TEST is in progress
7346
CB-TSTstop FLT.
OUT_Ev
CB-TEST canceled due to Power Sys. Fault
7347
CB-TSTstop OPEN
OUT_Ev
CB-TEST canceled due to CB already OPEN
7348
CB-TSTstop NOTr
OUT_Ev
CB-TEST canceled due to CB was NOT READY
7349
CB-TSTstop CLOS
OUT_Ev
CB-TEST canceled due to CB stayed CLOSED
7350
CB-TST .OK.
OUT_Ev
CB-TEST was successful