Functions
2.24 Monitoring Functions
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
433
Table 2-17
Summary of Malfunction Responses of the Device
Monitoring
Possible Causes
Malfunction Re-
sponse
Indication (No.)
Output
Loss of aux. voltage
External (aux. voltage)
internal (converter)
Device out of operation,
alarm if necessary
all LEDs dark
„Error 5V“ (144)
DOK
drops
out
Measured value
acquisition
Internal (converter or refer-
ence voltage)
Protection out of opera-
tion, indication
LED „ERROR“
„Error A/D-conv.“ (181)
DOK
drops
out
Buffer battery
Internal (buffer battery)
Indication
„Fail Battery“ (177)
As allocated
Hardware watchdog
Internal (processor failure)
Device out of operation LED „ERROR“
DOK
drops
out
Software watchdog
Internal (program sequence) Restart attempt
LED „ERROR“
DOK
drops
out
Main memory
Internal (RAM)
Restart attempt
, abort
restart
Device out of operation
LED flashes
DOK
drops
out
Program memory
Internal (EPROM)
Restart attempt
LED „ERROR“
DOK
drops
out
Parameter memory
Internal
(flash EPROM or RAM)
Restart attempt
LED „ERROR“
DOK
drops
out
Sampling frequency
Internal (master clock)
Restart attempt
LED „ERROR“
DOK
drops
out
1 A/5 A setting
Jumper setting 1/5 A incorrect Indications:
Protection out of opera-
tion
„Error1A/5Awrong“
(192) „Error A/D-conv.“
(181)
LED „ERROR“
DOK
drops
out
Adjustment values
Internal (EEPROM or RAM)
Indication:
using default values
„Alarm adjustm.“ (193) As allocated
Earth current transform-
er sensitive/insensitive
I/O module does not comply
with the order number (MLFB)
of the device
Indications:
Protection out of opera-
tion
„Error neutralCT“
(194)„Error A/D-conv.“
(181)
LED „ERROR“
DOK
drops
out
Modules
Module does not comply with
order number (MLFB).
Indications:
Protection out of opera-
tion
„Error board1...7“ (No
183 ... 189)
and if applicable
„Error A/D-conv.“. (181)
DOK
drops
out
Current sum
Internal (measured value ac-
quisition)
Indication
Total blocking of differ-
ential protection
„Failure
Σ
i“ (289)
As allocated
Current symmetry
External (power system or
current transformer)
Indication
„Fail I balance“ (163)
As allocated
Broken wire
External (power system or
current transformer)
Indication
Phase-selective block-
ing of differential protec-
tion
„Broken Iwire L1“ (290),
„Broken Iwire L2“ (291),
„Broken Iwire L3“ (292)
As allocated
Voltage sum
Internal (measured value
acquisition)
Indication
„Fail
Σ
U Ph-E“ (165)
As allocated
Voltage symmetry
External (power system or
voltage transformer)
Indication
„Fail U balance“ (167)
As allocated
Voltage phase
sequence
External (power system or
connection)
Indication
„Fail Ph. Seq.“ (171)
As allocated