4 PROFINET IO Diagnosis
4.2 PROFINET IO Error Indication in the SIPROTEC 4 Device
91
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
4.2
PROFINET IO Error Indication in the SIPROTEC 4 Device
Display in DIGSI
The indication
SysIntErr.
(error of the system interface) is used for the PROFINET IO error indication. In the
DIGSI configuration matrix, this indication is available in the
Protocol
menu.
Figure 4-4
Error Indication of the System Interface (DIGSI)
The following table contains the description of the error indication:
Table 4-1
Error Indication SysIntErr.
Error
indication
After restart
ON
→
OFF
OFF
→
ON
SysIntErr.
= ON
Change to OFF if the IO
controller is connected and cyclic
IO data are exchanged.
Change to ON if the IO controller
is not connected anymore or if no
cyclic data are exchanged any-
more.