2 PROFINET IO in SIPROTEC
2.4 IO Modules
31
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
IO Module Single-Point Indications 32
IO Module Double-Point Indications 04
Figure 2-15
Double-Point indication 04
Single-point indications 32
Category in the hardware catalog
Input data
Data type
32 single-point indications; see Chapter 2.3.1
Data size
4 bytes
Acyclic reading/writing of data
None
Parameters
Each single-point indication can be assigned to the process alarm
(see Chapter 2.7).
Default setting: all not assigned
Double-point indications 04
Category in the hardware catalog
Input data
Data type
4 double-point indications; see Chapter 2.3.3
Data size
1 byte
Acyclic reading/writing of data
None
Parameters
Each single-point indication can be assigned to the process alarm
(see Chapter 2.7).
Default setting: all not assigned