Storing a Device
How to procede
²
SIPROTEC devices must be stored in rooms which are clean and dry. Devices or associated replacement
modules must be stored at a temperature of –25 °C to +55 °C (-13 °F to 131 °F).
²
The relative humidity must be at a level where condensate and ice is prevented from forming.
²
Siemens recommends that you observe a restricted storage temperature range of +10 °C to +35 °C (50 °F
to 95 °F), in order to prevent the capacitors used in the power supply from aging prematurely.