Function
2.2 Protection
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
48
2.2.1
Phase Overcurrent Protection
This device supplies 2 stages of definite time phase overcurrent protection.
Figure 2-25
Logic Diagram of the Phase Overcurrent Protection
1.Compound voltage control can be enabled or disabled by setting the parameter
9001 Compound Voltage
Control
to
YES
or
NO
.
2. PT broken wire cannot block the phase overcurrent protection.
3. After the trip signal is released, the dropout of the voltage signal cannot reset the trip signal, only current
dropout can reset the trip signal.