4.5 Time Overcurrent Protection for Earth Current (Starpoint Current)
453
7UT613/63x Manual
C53000-G1176-C160-2
4.5
Time Overcurrent Protection for Earth Current (Starpoint Current)
Characteristics
Current Stages
Definite-time stages
DT
I
E
>>,
I
E
>
Inverse time stages
(acc. to IEC or ANSI)
IT
I
EP
The same characteristics apply as for time
overcurrent protection for phase and residual
currents in accordance with the preceding
section
Reset characteristics
with disk emulation
IT
The same reset time characteristics apply as
for time overcurrent protection for phase and
residual currents in accordance with the pre-
ceding section
High current stage
I
E
>>
0.05 A to 35.00 A
1)
or
∞
(ineffective)
Steps 0.01 A
T
I
E>>
0.00 s to 60.00 s
or
∞
(no trip)
Steps 0.01 s
Definite time current element
(50Ns-2, 50Ns-1)
I
E
>
0.05 A to 35.00 A
1)
or
∞
(ineffective)
Steps 0.01 A
T
I
E>
0.00 s to 60.00 s
or
∞
(no trip)
Steps 0.01 s
Inverse current element (51Ns-
IEC)
I
EP
0.05 A to 4.00 A
1)
Steps 0.01 A
T
I
EP
0.05 s to 3.20 s
or
∞
(no trip)
Steps 0.01 s
Inverse current element (51Ns-
ANSI)
I
EP
0.05 A to 4.00 A
1)
Steps 0.01 A
D
I
EP
0.50 s to 15.0 s
or
∞
(no trip)
Steps 0.01 s
Tolerances with definite time
currents
3 % of setting value or 1 % nominal current
times
1 % of setting value or 10 ms
Tolerances with inverse time (IEC)
currents
Pickup with
1.05
≤
I
/
I
EP
≤
1.15;
times
5 %
±
15 ms
5 %
±
45 ms
at f
N
= 50/60 Hz
for f
N
= 16.7 Hz
for 2
≤
I
/
I
EP
≤
20
and T
I
EP
/s
≥
1
Tolerances with inverse time (ANSI)
times
5 %
±
15 ms
5 %
±
45 ms
at f
N
= 50/60 Hz
for f
N
= 16.7 Hz
for 2
≤
I
/
I
EP
≤
20
and D
I
EP
/s
≥
1
The set times are pure delay times.
1)
Secondary values for
I
N
= 1 A; for
I
N
= 5 A the currents must be multiplied by 5.
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...