2 Functions
222
7UT613/63x Manual
C53000-G1176-C160-2
Motor Startup
On startup of electrical machines the overtemperature calculated by the thermal
replica may exceed the alarm overtemperature or even the trip overtemperature. In
order to avoid an alarm or trip, the starting current is acquired and the resulting in-
crease of temperature rise is suppressed. This means that the calculated temperature
rise is kept constant as long as the starting current is detected.
Emergency Start-
ing of Machines
When machines must be started for emergency reasons, operating temperature
above the maximum permissible operating temperature can be allowed by blocking
the tripping signal via a binary input (
„>Emer.Start O/L“
). After startup and
dropout of the binary input, the thermal replica may still be greater than the trip tem-
perature rise. Therefore the thermal replica features a settable run-on time (
T
EMERGENCY
) which is started when the binary input drops out. It also suppresses the
trip command. Tripping by the overload protection will be defeated until the time inter-
val has lapsed. This binary input only affects the trip command. There is no effect on
fault recording, nor does the thermal replica reset.
Figure 2-98
Logic diagram of the thermal overload protection (simplified)
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...