Functions
260
7UM62 Manual
C53000-G1176-C149-3
The closest standard value of 39 k
Ω
is selected; the power is:
2.39.2.1 Settings for the Trip Circuit Supervision
2.39.2.2 Information
R
max
110 V
19 V
–
1.8 mA
----------------------------------
è
ø
æ
ö
500
Ω
–
50.1 k
Ω
=
=
R
min
500
Ω
110 V
2 V
–
2 V
------------------------------
è
ø
æ
ö
⋅
27 k
Ω
=
=
R
R
max
R
min
+
2
--------------------------------
38.6 k
Ω
=
=
P
R
110 V
39 k
Ω
0.5 k
Ω
+
----------------------------------------
è
ø
æ
ö
2
39 k
Ω
⋅
=
P
R
0.3 W
≥
Addr.
Setting Title
Setting Options
Default Setting
Comments
8201
TRIP Cir. SUP.
OFF
ON
OFF
TRIP Circuit Supervision
F.No.
Alarm
Comments
06851 >BLOCK TripC
>BLOCK Trip circuit supervision
06853 >TripC brk rel.
>Trip circuit supervision: breaker relay
06852 >TripC trip rel
>Trip circuit supervision: trip relay
06861 TripC OFF
Trip circuit supervision OFF
06862 TripC BLOCKED
Trip circuit supervision is BLOCKED
06863 TripC ACTIVE
Trip circuit supervision is ACTIVE
06864 TripC ProgFail
Trip Circuit blk. Bin. input is not set
06865 FAIL: Trip cir.
Failure Trip Circuit