Functions
188
7UM62 Manual
C53000-G1176-C149-3
Use as Earth Short-
Circuit Protection
For low-voltage machines with neutral conductor incorporated in cables or machines
with low-impedance earthed starpoint, the time-overcurrent protection of the phase
branches already is a short-circuit to earth protection, as the short-circuit to earth
current also flows through the faulty phase. If the sensitive earth current detection
nevertheless shall be used as short-circuit to earth protection, an external
intermediate transformer must be used to ensure that the short-circuit current does not
exceed the thermal limit values (15 A continuous, 100 A for < 10 s, 300 A for < 1 s) of
this measuring input.
2.27.2.1 Settings of the Sensitive Earth Fault Protection
2.27.2.2 Information for the Sensitive Earth Current Detection
Addr.
Setting Title
Setting Options
Default Setting
Comments
5101
O/C PROT. Iee>
OFF
ON
Block relay for trip com-
mands
OFF
Sensitive Earth Current Protec-
tion
5102
IEE>
2..1000 mA
10 mA
Iee> Pickup
5103
T IEE>
0.00..60.00 sec;
∞
5.00 sec
T Iee> Time delay
5104
IEE>>
2..1000 mA
23 mA
Iee>> Pickup
5105
T IEE>>
0.00..60.00 sec;
∞
1.00 sec
T Iee>> Time Delay
5106
IEE<
1.5..50.0 mA; 0
0.0 mA
Iee< Pickup (Interrupted Circuit)
F.No.
Alarm
Comments
01231 >BLOCK Sens. E
>BLOCK sensitiv earth current prot.
01203 >BLOCK IEE>
>BLOCK IEE>
01202 >BLOCK IEE>>
>BLOCK IEE>>
01232 IEE OFF
Earth current prot. is swiched OFF
01233 IEE BLOCKED
Earth current prot. is BLOCKED
01234 IEE ACTIVE
Earth current prot. is ACTIVE
01224 IEE> picked up
IEE> picked up
01221 IEE>> picked up
IEE>> picked up
01226 IEE> TRIP
IEE> TRIP
01223 IEE>> TRIP
IEE>> TRIP
05396 Fail. REF Iee<
Failure R/E/F protection Iee<