Functions
174
7UM62 Manual
C53000-G1176-C149-3
The vector jump function becomes ineffective on leaving the permissible frequency
band. The same is true for the voltage, for which the limiting parameters are
and
On violation of the frequency or voltage band, the logic generates a logical “1”, and the
reset input is continuously active. The result of the vector jump measurement is sup-
pressed. If, for instance, the voltage is connected, and the frequency band is correct,
the logical “1” changes to “0”. The timer
with reset delay keeps the reset in-
put active for a certain time, and thus prevents a pickup caused by the vector jump
function.
If a short-circuit causes the voltage to drop abruptly to a low value, the reset input is
immediately activated to block the function. The vector jump function is thus prevented
from causing a trip.
Figure 2-81
Logic Diagram of the Vector Jump Detection
2.25.2 Setting Hints
General
The vector jump function is only effective and accessible if address
has been set to
during configuration.
Address
is used to switch the function ON or OFF, or to block
only the trip command (Block relay).
4602 DELTA PHI
5583
VEC JMP BLOCKED
4605 U MIN
4606 U MAX
4607 T BLOCK
5586
VEC JUMP pickup
5587
VEC JUMP TRIP
5585
VEC JUMP Range
4603 T DELTA PHI
4604 T RESET
>VEC JUMP block
5581
Angle comparison with
three measuring points
n-2, n-1, n
∆φ
n
+
f
rated
3 Hz
f
rated
3 Hz
f
f
U1
U1
OR
0
T
OR
S
R
Q
f<(f
rated
-3 Hz)
f>(f
rated
+3 Hz)
U1<U MIN
U1>U MAX
Tripping
matrix
Tmin TRIP
CMD